Modscan32 Software Manual

Modscan32 Software Manual 3,6/5 1034 votes

Summary Modscan32 is a 32-little bit Windows program (Modscan64 is certainly comparable, but for 64-little bit Home windows) that serves as a Modbus expert gadget for process assessment and carrying out Modbus serial ánd TCP/IP data selection by polling át user-defined intervals down to milliseconds. It can acquire information in integer, unsignéd decimal, and floating point forms. It furthermore supports register writes. The servant response time and delay between polls are user selectable. Continental Control Systems does market any software products. Please contact the manufacturer straight for details on their numerous variations and pricing.

More details may end up being discovered at the using links:. Modscan32 will be accessible in a couple of different versions. Contact WinTECH Software Style to purchase this software.

The cost is $65 for the single-user fundamental version; or $110 for the Professional edition that includes MMI (e.g. Pattern graphs) and OLE features for Modscan32 information accessibility by Excel'beds VBA macro vocabulary. For even more information on making use of Modscan32 with the WattNode ® Modbus ® meter notice. Pros. Supports Modbus/TCP, Remote Telnet Machine (for Ethérnet/RS-485 SDAs) and a variety of additional connection sorts (like Telnet) simply because properly as immediate serial port (COM interface) connections.

Has optional handshake series control which may be required for older RS-232/RS-485 adapters utilized on legacy PC serial slots that don't deal with RS-485 coach driver handle automatically. Offers a “hex drop” screen mode which will be useful for trouble-shooting marketing communications troubles. It can become quickly fixed up to go through a variety of registers of the exact same type (vs. Ocean Controls approach of setting up personal tags which can be more tedious and time-consuming). Cons. Modscan32't Point Kind selection defaults to “Coils Position” which requires changing it to “Keeping Sign up” before a WattNode meter't sign up can be polled.

Modscan32 is certainly a device intended mainly for designers and IT folks who are usually familiar with the basics of protocols like Modbus. Captured text documents are not in standard CSV (Comma Separated Values) structure. The non-standard data format requires making use of Excel's Import Wizard which requires more steps.

Nevertheless, there is definitely a work-aróund for this (notice csv.exe below). Poor trend graphing capability. Challenging to arranged up and change.

When attempting to change a worth, the focus doesn't begin in the value text package, needing an extra click. When exhibiting floating stage beliefs, if the window isn'testosterone levels tall good enough, Modscan32 shows several columns, but the text message from a single line overlaps the next.

Application Description. ModScan32 is an expanded version of the popular 16-bit application ModScan.It is a Win32 application designed to operate as a MODBUS Master device for accessing data points in a connected PLC compatible slave device. Modbus Protocol User Guide Revision C January 3, 2006 Part Number GC-800-250. Grid Connect warrants the media containing software and technical information to be free from. This manual provides detailed operation and setup information for the XPort-03 Device Server with Modbus. Errata 1010FMA-56 January 2012 E1 Errata ModBus Register Map Additions and Fault Bit Decoding List Update The following applies to the 1015N-5M ModBus manual (Revision 1) and Modscan32 Quick Start Guide. B&B Electronics MODSCAN32 - Manual • User guide • Download PDF for free and without registration!

When showing floating point values, Modscan32 shows blank ranges between every additional value. Works only on Windows. No Linux or Apple OS edition is available. Quick Start Guidebook This section represents how to connect and configure á WattNode méter with Modscan32, set the CtAmps, and create some fundamental dimensions. It also discusses how to use ModScan32 to communicate with WattNode meters via the two almost all common forms of SDA (Serial Gadget Adaptér):. A USB/RS-485 adapter. An Ethernet/RS-485 adapter.

ModScan32 is usually for polling and documenting data readings from slave products that use the Modbus communications protocol. It can furthermore compose to registers to configure settings in Modbus slaves. The free of charge demo edition can become helpful for isolating the cause of issues when a consumer is using another third-party Modbus get better at system that is definitely misconfigured or that offers a software insect by enabling them to compare the blood pressure measurements acquired with their softwaré versus the psychic readings obtained with ModScan32.

ModScan32 can furthermore provide as a simple data logger for taking data in text message data files. Since the demonstration version can become freely distributed, an installer can use it for the moment or two that it requires to configure thé CT amps rankings via the WattNode meter's CtAmps signs up and to verify that the Modbus communications is functioning.

Software Manual Template

ModScan32 operates on most versions of MS Windows, including Home windows XP. ModScan32 can communicate with the Módbus WattNode meter using SDAs that assistance RS-48.

WinTech's time-limited free of charge demo version of ModScan32 runs for a couple of mins, which is definitely long enough to configure á WattNode méter's CtAmps registers. To eliminate the period limitation, the demonstration can be authorized by entering a permit key attained from WinTech.

As of Q3 2009, the basic version expenses $65 and the Professional version costs $110. Both variations of ModScan32 support looking at and updating numeric register values and taking information to text documents that can become brought in into spreadsheet programs like Excel. The Professional version contains additional functions that support observing the information as trend ranges on basic graphical charts and exporting data to OLE customer programs. Installing it is as easy as installing the free demonstration Modscan32.zip file and replicating its contents into a folder named, “C:Modscan32”.

How to use Modscan32 with a COM slot to Configure thé WattNode méter's CT Amps Configurations The installation details fór USB/RS-485 adapters varies depending on the particular model but the primary steps are usually the same regardless of model. There is usually a video-onIy (no sound-tráck) that shows this procedure at:. Connect strength supply if required. Take note that most USB/RS-485 adapters are run by the USB sponsor and perform not require an external power source. Insert the adapter.

Windows “New Equipment Device Wizard” should appear and prompt for the location of the gadget driver data files which are usually usually on the software submission Compact disc that arrived with the adapter. After adhering to the prompts, if the adapter motorist installed correctly, you should notice it shown under the Home windows Device Manager's Slots (COM LPT) listing. Generally it will include “RS-485” in the name. Note the COM interface amount that Home windows assigned to the gadget. Use Home windows Explorer to view the folder where Modscan32 is set up and begin Modscan32 by dual clicking the Módscan32.exe executable.

Once Modscan32 begins up a “Modsca1” record screen should appear. Enter the WattNodé meter's servant tackle (arranged with the DIP fuses) in the “Gadget Id” package. For example if the meter'beds DIP buttons 2 to 7 are away and 1 is definitely on, enter a worth of 1. Next specify that you want to examine the CT Amps signs up: Under “Modbus Point Type”, choose “Holding Register”. Undér “Address” enter “1603”. Under “Length” get into “4”. This selects the worldwide CT Amps sign up CtAmps and thé CT Amps signs up for each of the three phases ( CtAmpsA, CtAmpsB, ánd CtAmpsC).

Select “Connection->Connect” and under “Connect Making use of”, select the COM interface number of your adapter and make certain the baud price fits the WattNode méter's (9600 if DIP change 8 is certainly away; 19200 if it can be on). No equipment flow handle is needed for most USB/RS-485 adapters which have the “auto-enable” feature. Click on the “Process Choices” button and create certain that the “Transmitting Setting” is arranged to “RTU”.

Thé “Slave Timeout” shouId be “1000 ms”. And for the “Delay Between Polls”, 500 ms. Is definitely a sensible poll rate. Close the dialogs by clicking on the “Okay” button and at that point, Modscan32 should begin polling the WattNodé Modbus meter. Thé “Number of PoIls” will begin incrementing and if the RS-485 user interface is correctly linked to the adaptér, the “Number óf Valid Slave Responses” should increment at the exact same rate. To established the CT Amps configurations to various values for each óf the three phases, double-click on the displayed sign up which will take up a “Write Register” dialog that enables you to enter the fresh worth.

Enter the CT ranking in amps and click “Revise”. The dialog will close and the displayed value of the matching CT Amps sign up should change appropriately. If the CT ranking is certainly the exact same for all three phases, you can established all three to the exact same value at as soon as by composing to the Worldwide CT Amps register (1603). When you are usually done you can choose “File->Save As” and identify the document name “CtAmps” to save the changes you made so the following time you run Modscan32, you can choose “File” and click on “CtAmps” so you don't possess to re-enter the same register address etc. How to Go through All WattNode Registers Making use of Preconfigured Modscan32 Record Documents Since there is definitely no common standard for mapping Modbus register handles onto specific slave gadget readings (because the Modbus regular just specifies the low-level marketing communications data transportation layer, not really the high-level software level or data sorts), some customization will be needed in order to indicate which information signs up should be polled from a particular slave gadget and how the data should be formatted. ModScan32 will save this configuration data in special “documents”, where each document corresponds to a continuous collection of Modbus keeping signs up. Each record window shows register information of the same kind and file format (flying point or 16-little bit integer etc.).

To save time in configuring Modscan32, preconfigured ModScan32 papers are obtainable from CCS in a Squat archive document called, “Modscan32ForWattNode.diddly”. These documents are preconfigured for obtaining the particular registers comprising the WattNode meter information and believe that the meter is certainly assigned a slave tackle of 1 and that its baud price is fixed to 19200 (i actually.elizabeth. The meter'h DIP changes 1 and 8 are usually on, and 2 to 7 are off). The WattNodéAutoStart.tst Auto-stárt configuration file assumes that thé USB/RS-485 adapter is definitely designated to the PC's COM10 serial slot (this can simply be transformed as referred to below). The material of the Módscan32ForWattNode.diddly file should become duplicated to the exact same folder, “M:Modscan32”, that you created with Home windows Explorer when you set up Modscan32. There are usually seven custom made configuration files for the WattNode meter:. Master of science32frm.cfg ” This document informs Modscan32 to automatically load the settings contained in the WattNodeAutoStart.txt file at stárt-up.

WattNodéAutoStart.tst - This can be the Auto-start settings document that informs Modscan32 which COM slot the meter is linked to and which paperwork to automatically open up when it begins upward. WattNodeBasicFloatOutputs - This Modscan32 record displays energy, energy and voltage float registers 1001 to 1034. WattNodeAdvancedFloatOutputs - This Modscan32 record displays advanced energy, power and requirement float signs up 1112 to 1176. WattNodeConfiguration - This Modscan32 document displays settings integer signs up 1601 to 1621.

WattNodeCustomerDiagnostics - This Modscan32 record displays consumer diagnostic integer signs up 1707 to 1722. WattNodePowerTrendGraph - This Modscan32 record shows the stage A, M, Chemical and Need power float registers (1011, 1013, 1015 and 1169) as reddish, green, azure and violet traces, respectively on a craze chart. After copying the WattNode meter construction data files from the Módscan32ForWattNode.squat file into the same D:Modscan32 folder that you installed the Modscan32 system (overwriting the present configuration data files), you can start Modscan32 by double-clicking on Modscan32.exe. Upon starting, Modscan32 will display some “Registration” discussion containers.

After pressing “OK” to each discussion, Modscan32 will then test to link to the méter and if successful, it will screen and upgrade the five docs detailed above with fresh information every 2 or 3 mere seconds. If yóur USB/RS-485 adapter has been assigned to a different COM interface after that an error information will show up that states, “Connection Failed!”. In that case, you need to tell Modscan32 which COM interface to use by clicking the Link menu club product and selecting the “Connect” product from the checklist. A dialog container that shows up with a “Connect Making use of:” checklist package that allows you to choose the proper COM slot (Take note: The Home windows Device Manager applet shows all serial COM ports under the Ports device team). After you've chosen the right port, click on Fine and Modscan32 should then start polling the WattNodé meter and updating the displayed records after a few secs.

If your meter utilizes a CT rated for other than the defauIt of 5 amps, you can reconfigure it for the proper CT rating by hitting on the WattNodeConfiguration record watch. Integer register 1603 can be the worldwide CT amps register which enables you to arranged the CT rating for all three phases if they all have got the same ranking. In cases where in different ways scored CTs are usually used on each phase, signs up 1604, 1605 and 1606 enable assigning each CT amps rating for stages A, N and M respectively. If any stage inputs are not used and are usually still left unterminated (no shorting wire) then they can result in little but unwanted powers to become accumulated credited to run away electrical fields.

This can be prevented by setting up their CT amps sign up to focus, like the global CT amps register (Note: The phase LEDs may nevertheless occasionally flash reddish colored but no energy is gathered if the CtAmps sign up can be zero). To modify the worth of a sign up, double-click the displayed register worth and a discussion container will show up that allows you get into the new value. After entering the new value, click the “Update” switch and the brand-new setting will become written to the méter. Modscan32 can sign the data readings for any óf the displayed docs into text files containing of space-separated ideals. This is certainly done by clicking on on the record to bring it to thé foreground and then selecting “Setup” from the menu bar and then “Text Capturé”. A “Savé As” dialog will appear that allows you to stipulate the text message file title and area.

After specifying the file name, another dialog will show up that allows you select how usually to store the information. To stop collecting WattNode information, go for “Setup” and after that “Capture Off”. Note that you can identify a various data document name and start and cease logging data individually for each record.

Since the information is captured as a text document, you should use the “txt” document name expansion for information file brands. To import a taken text document with Excel, go for “Open” and browse to the Módscan32 folder and select Excels dialog option including “.txt” from the “Data files of Type” checklist package. A discussion will show up that enables you tell Excel precisely how to import the information.

Select the “Delimited” choice and click “Next”; then check out the “Space” package and Excel provides you with an example of the data that permits selecting columns you put on't wish to transfer (at the.h. The redundant time areas). After you click “Finish” the information will end up being brought in into the spréadsheet.

If you're acquainted with how to operate Windows console programs, you can use a energy known as csv.exe (integrated in the zip document below) that changes from Modscan32'beds data structure into regular comma-separated values (CSV) format that can be taken into Excel without using the Excel information import sorcerer. The csv.exe electricity processes a information file you earlier captured with Modscan32 and changes it tó CSV format thát Excel automatically identifies. Whenever you alter the Modscan32 “Connection” settings you should conserve them to thé WattNodeAutoStart.tst Autó-start configuration file by choosing “Link”, “Car Start”, “Conserve Config” and selecting the WattNodeAutoStart.tst document title. This method, the following period you start Modscan32, it will be able to restore the same communications connection instantly. The appearance of the WattNodePowerTrendGraph document can end up being customized by right-cIicking it. A Development Chart Qualities discussion will appear that lets you personalize the search for (or pen) colors and designate a data register supply to a specific trace.

Modscan32 Free Download Software

Personal footprints can be allowed or disabled by clicking the matching pen button and looking at or un-chécking the Enabled package. The register address is definitely came into in the “Point Tackle:” industry.

Modscan32 Software Free Download

The format of the information under the “Format” list box should go with the kind of register you desire to give to the track. It will be easiest to make use of the WattNode drift (vs. Integer) signs up for craze charts (and also for capturing data blood pressure measurements to text data files).

After making adjustments to the trend chart you should conserve them by selecting “File” and “Savé” so it wiIl reappear the exact same way the following time you start Modscan32. To include a brand-new Trend Graph, click on “File”, “Custom Fórm” and “Create”. After that use the mouse to establish a square region for the MMI item in the record that appears. Click on on the stage where you want the higher left corner to show up and while keeping down the mouse key, move the cursor tó the lower correct hand part. A “Custom Display” dialog box will then show up that lets you select the “Simple Trend Chart”. You can after that right click the causing graph to personalize the “Pen” qualities that figure out the displayed remnants. How to make use of Modscan32 with an Ethernet/RS-485 Serial Gadget Adapter The pursuing explains how to connect to a WattNode meter making use of an Ethernet/RS-485 SDA.

You can disregard this section if you are usually making use of á USB/RS-485 adapter. Since the WattNodeAutoStart.txt Auto-start settings file was set up for á USB/RS-485 adapter on the COM10 port, the “Connection Failed!” error information will show up when you launch Modscan32. To fix this, select “Connect” and undér the “Connect Making use of:” listing box, select “Remote TELNET Server” and enter the TCP/IP tackle and port of yóur SDA in thé “IP Tackle:” and “Service Port:” boxes, respectively. These beliefs should match the ones you designated to yóur SDA. Refer tó your SDA manuaI for the method for assigning the SDA tackle, slot and serial communications parameters.

This is definitely usually carried out with a Internet web browser but the exact details differ based on SDA make and model. Summary Modscan32 is a simple but useful plan and the price is fair compared to most SCADA or Information Logger software.

If you just require to use it for a moment or two for assigning the CtAmps construction registers then the free of charge demo version should become adequate. Modscan32 will work with any Modbus slave device that conforms to the Modbus marketing communications process (find ).

By using it in association with the Modscan32 configuration files offered by CCS, it provides a quick, vendor-neutral method to verify that a strength monitoring set up with Modbus WattNode metres is working properly. The amount below exhibits how Modscan32 presents the WattNode meter information in both numeric and graphic form. C windows prefetch readyboot readyboot etl.